除塵系統315-2 拖2個ET200m站點,意外停機,后來重啟CPU 好了,不知道原因。故障時候SF BF STOP 燈常亮。請各位老師不吝賜教,謝謝!

Diagnostic buffer of module CPU 315-2 DP

Order No./ Description         Component                      Version                      
6ES7 315-2AH14-0AB0            Hardware                       6                            
- - -                          Firmware                       V 3.3.11                      
Boot Loader                    Firmware expansion             A 37.12.12                  

Rack:                          0
Slot:                          2


Serial number: S C-F6DW50132015


Event 1 of 10:  Event ID 16# 4302
Mode transition from STARTUP to RUN
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STARTUP (warm restart)
Requested operating mode: RUN
Incoming event
08:30:11.743 AM  03/10/1995
(Coding: 16# 4302  FF68  C700  0000  0813  7713)


Event 2 of 10:  Event ID 16# 1381
Request for manual warm restart
Startup information:
- Startup without modified system configuration
- No difference between setpoint and actual configuration
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Requested OB: Startup OB (OB100)
OB not found, or disabled, or cannot be started in the in the current operating mode
Incoming event
08:30:11.742 AM  03/10/1995
(Coding: 16# 1381  FE64  C772  0000  0813  7713)


Event 3 of 10:  Event ID 16# 4301
Mode transition from STOP to STARTUP
Startup information:
- Time for time stamp at the last backed up power on
- Single processor operation
Current/last startup type:
- Warm restart triggered by switch setting; last power on backed up
Permissibility of certain startup types:
- Manual warm restart permitted
- Automatic warm restart permitted
Last valid operation or setting of the automatic startup type at power on:
- Warm restart triggered by switch setting; last power on backed up
Previous operating mode: STOP (internal)
Requested operating mode: STARTUP (warm restart)
Incoming event
08:30:11.653 AM  03/10/1995
(Coding: 16# 4301  FF46  C772  0000  0813  7713)


Event 4 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    7
DP master system ID:      1
Log. base address of the DP slave: Input address:  2044
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
08:19:18.320 AM  03/10/1995
(Coding: 16# 38C4  FE56  C054  07FF  07FC  0107)


Event 5 of 10:  Event ID 16# 38C4
Distributed I/Os: station return
Address of the affected DP slave: station number:    6
DP master system ID:      1
Log. base address of the DP slave: Input address:  2046
Log. base address of the DP master:   2047
Requested OB: Rack failure OB (OB86)
OB not found, or disabled, or cannot be started in the current operating mode
External error, Outgoing event
08:19:08.663 AM  03/10/1995
(Coding: 16# 38C4  FE56  C054  07FF  07FE  0106)


Event 6 of 10:  Event ID 16# 5371
Distributed I/Os: End of the synchronization with a DP master/IO controller  on slot   2
Number of distributed stations:   2
Incoming event
08:19:07.904 AM  03/10/1995
(Coding: 16# 5371  FF02  C150  0002  0000  0000)


Event 7 of 10:  Event ID 16# 4358
All modules are ready for operation
Operating mode: STOP (internal)
Incoming event
08:19:05.462 AM  03/10/1995
(Coding: 16# 4358  FF44  0000  0000  0000  0000)


Event 8 of 10:  Event ID 16# 4357
Module monitoring time started
Operating mode: STOP (internal)
Incoming event
08:19:04.184 AM  03/10/1995
(Coding: 16# 4357  FF44  0000  0000  0000  0000)


Event 9 of 10:  Event ID 16# 430E
Memory reset executed
Previous operating mode: STOP (memory reset)
Requested operating mode: STOP (own initialization)
Incoming event
08:19:00.952 AM  03/10/1995
(Coding: 16# 430E  FF23  0000  0000  0000  0000)


Event 10 of 10:  Event ID 16# 4546
STOP caused by CPU memory management
Previous operating mode: STOP (own initialization)
Requested operating mode: STOP (memory reset)
Internal error, Incoming event
08:18:58.337 AM  03/10/1995
(Coding: 16# 4546  FF32  C0C0  8FFE  0000  0000)

volcanol
級別: 探索解密
精華主題: 0
發帖數量: 17 個
工控威望: 107 點
下載積分: 835 分
在線時間: 11(小時)
注冊時間: 2010-01-04
最后登錄: 2024-07-17
查看volcanol的 主題 / 回貼
1樓  發表于: 2016-12-24 13:54
DP從站丟失引起機架錯誤,導致停機。

如果要避免停機增加OB86組織塊,并下載到PLC中,可以避免停機。

但是不能消除DP從站丟失的故障,檢查DP通訊。
guang886622
級別: 略有小成
精華主題: 0
發帖數量: 191 個
工控威望: 304 點
下載積分: 17781 分
在線時間: 110(小時)
注冊時間: 2013-02-03
最后登錄: 2024-03-14
查看guang886622的 主題 / 回貼
2樓  發表于: 2016-12-24 17:48
是不是DP通訊頭有問題,之前我這里也出現故障,更換DP通訊頭好了

主站蜘蛛池模板: 欧美三级在线播放 | 97蜜桃| 色一情一伦一区二区三 | 最新韩剧美剧超清全集 | 欧美国产日韩1区俺去了 | 国产日韩一区二区三区高清 | 国产精品思思在线 | 大陆aⅴ国 | 国内精品一区二区三区在线观看 | 欧美乱妇日本无乱码特黄大片 | 欧美精品亚洲精品日韩传电影 | 三年在线观看免费完整版中文 | 国产精品三级在线看免费看 | 午夜免费一级视频 | 成人国产精品日本在线观看 | 女人扒开 | 樱花草www日本在 | 精品日韩视频一区二区三 | 精品国产一区二区三区a | 国产极品精品免费视频能看 | 国产看片短视 | 爽黄的免费视频 | 日韩免费视频 | 朝鲜女人大白屁股ass | 国产高清 | 国产在线精品一区二区三区 | 欧美激情视频在线播放全球共享 | 日韩亚洲产在线观看 | 观看www成人影院 | 欧美性播放中国 | 午夜视频 | 中文字幕日本有码视频在线 | 电视剧大全免费全集观看 | 日本高清在 | 日本高清视频色www在线观看 | 成人性欧美 | 91精品在线国产 | 欧美日韩国产免费一区二区三区 | 亚洲综合精品网站在线观看 | 99精品全国免费观看视频 | 在线观看日韩视频 |